In the past, a corner of the cellar was enough for the oil boiler and water meter in a detached house. Today, a heat pump, buffer tank, hot water cylinder, ventilation unit, inverter, battery storage and meter cabinet all come together, and suddenly space is tight. If you want to plan a plant room, you should therefore decide early on which devices will go into it, how much space they need for operation and maintenance and where the room will be located in the house, because the floor area can hardly be enlarged once the shell is built.
In this guide, you will learn which components are typically installed in a plant room today, how large it should be and which location makes sense. We also look at the requirements for utility connections, fireplaces and propane heat pumps and show what to look out for in terms of water, electricity, noise and room temperature.
What belongs in a plant room today: heating, ventilation and power
In a new building with a heat pump and controlled residential ventilation, the plant room is the control centre of the house. It typically houses the indoor unit of the heat pump, a hot water cylinder and, if required, a buffer tank, the central ventilation unit with connections for outdoor air and exhaust air, and the heating circuit manifold. In addition, there are the utility connections for electricity, water and telecommunications, often the meter cabinet and, with a photovoltaic system, the inverter and battery storage.
There is a separate standard for utility connections, DIN 18012. It only provides for a separate utility connection room in buildings with more than five units. In a detached or two-family house, a utility connection wall or a utility connection recess is sufficient. In practice, this wall is usually located in the plant room, because water and electricity are distributed there anyway. Coordinate the location with your network operators early on, as they specify where the lines enter the building.
Compact units that combine ventilation with heat recovery, hot water production and a small exhaust air heat pump in one casing need little space. Such a compact ventilation unit is particularly suitable for well-insulated houses with a low heating demand.
Planning a plant room: how large does it need to be?
No standard prescribes a fixed minimum size for the plant room in a detached house. For a house with an air-to-water heat pump installed indoors, a cylinder and a ventilation unit, planning guides give a lower limit of around 6 to 8 square metres. Often, 10 to 12 square metres is more realistic once battery storage, a meter cabinet and space for maintenance are added. The old rule of thumb of 4 square metres dates from a time when only a boiler and a cylinder needed space.
| Component | Typical floor space | What to look out for |
|---|---|---|
| Heat pump, indoor installation | About 0.8 to 1.4 m² | Air ducts to the external wall, vibration isolation |
| Buffer tank or hot water cylinder | About 0.6 to 1.2 m² | Tilt height when bringing it in, weight when filled |
| Central ventilation unit | About 0.6 to 0.8 m² | Short outdoor and exhaust air ducts, condensate drain |
| Meter cabinet, inverter, battery storage | Wall space, depending on the system | Clearances as specified by the manufacturer and network operator |
These figures are guide values from planning guides. The data sheets for your devices are decisive, as they also state the required maintenance clearances. Ventilation units, for example, need space in front of the filter flap, and cylinders need access to the anode and sensors. Also pay attention to the ceiling height: tall cylinders have to be tilted when they are brought in, and the so-called tilt height can be greater than the installed height. You can read how much space a heat pump needs in an existing building in the guide Heat Pumps in Older Buildings.
The right location for the plant room in the house

A plant room does not have to be in the cellar. In houses without a cellar, a utility room on the ground floor often takes on this role, sometimes also a room in the attic or an extension. Short distances are crucial. The ventilation unit should be close to the external wall so that the outdoor air and exhaust air ducts remain short. These cold ducts must be insulated with a vapour-tight material, and every metre costs space and effort. You can read more about planning in the guide Planning Comfort Ventilation.
Proximity to the external wall also matters for the heat pump, either for the air ducts of an indoor unit or for short refrigerant or heating lines to the outdoor unit. If the room is located centrally in the house, the heating and drinking water pipes to the bathrooms are shorter. On the other hand, avoid a wall directly adjoining bedrooms. Compressors, pumps and fans generate noise, which is particularly disturbing at night.
Requirements for fireplaces, heat pumps and refrigerants
The combustion ordinances of the German federal states apply to boilers. According to the Model Combustion Ordinance, a separate boiler room is only required for solid fuel fireplaces with a rated output of more than 50 kilowatts; for gas and oil appliances, a special installation room is required above 100 kilowatts. These limits are not reached in a typical detached house. Nevertheless, even a small gas or pellet boiler has requirements for combustion air and flue gas routing, which the chimney sweep checks. The state ordinances may differ in detail.
With heat pumps, the refrigerant comes to the fore. Many current units use propane (R290), a flammable refrigerant that is heavier than air. The standard DIN EN 378 limits the permissible refrigerant charge depending on the size of the room and, depending on the case, requires ventilation or gas detection. Some R290 units are only intended for outdoor installation; in others, the refrigerant circuit is located exclusively in the outdoor unit. According to the product standard DIN EN 60335-2-40, there are no special requirements for the size of the installation room for a charge of up to 150 grams of propane; above that, they increase. Before planning, check what the manufacturer specifies for indoor installation.
In legal terms, the Building Modernisation Act (Gebäudemodernisierungsgesetz, GModG) has applied since 29 July 2026 and has replaced the Building Energy Act. The previous 65 per cent requirement for new heating systems has been dropped. For replacing the heating system in existing buildings, the Federal Funding for Efficient Buildings (BEG) remains in place according to the current status, with applications handled by KfW. In existing buildings, plan the plant room so that a heat pump with a cylinder can still fit in later. As of November 2026; KfW and BAFA publish the current conditions.
Water, electricity, noise and temperature in the plant room

A floor drain or at least a connection to the waste water pipe belongs in every plant room. The ventilation unit, heat pump and safety valves discharge condensate or water, and the system is drained during maintenance work. Condensate lines need a trap so that no sewer odours enter the ventilation unit. Plan enough sockets, good lighting and a network connection for controls that are operated online.
Vibration-isolated installation, flexible connections and a door with a seal help against noise. Room temperature is important for hygiene. According to DIN 1988-200, cold water pipes should not exceed 25 °C, otherwise the risk of Legionella increases. In a warm plant room with cylinders and heating pipes, this value is quickly reached. Insulate hot and cold pipes consistently and do not run cold water pipes directly next to heating pipes. Some specialist companies recommend temperature-controlled room ventilation. You can read more about this in the guide Drinking Water Hygiene.
Routing pipes and cables clearly
A well-planned plant room is still easy to understand years later. Route pipes in bundles and in parallel, label heating circuits, shut-off valves and fuses, and keep wall space free for later extensions, for example for a wallbox controller or larger battery storage.
Frequently asked questions
Can I put the plant room in the garage?
This is possible if the room remains frost-free and the devices are approved for the temperatures there. The disadvantage is often long pipe runs to bathrooms and heating circuits, which cause heat losses and waiting times for hot water.
Can the plant room also serve as a laundry room?
Yes, this is common in detached houses. Make sure there is sufficient distance from electrical installations, a floor drain and adequate dehumidification so that the humidity does not remain high permanently.
Do I need a window in the plant room?
Generally not for a heat pump and ventilation unit. This may be different for fireplaces or heat pumps with flammable refrigerant if the manufacturer requires ventilation. A window also makes it easier to bring in large devices.
How much space do the devices need between them?
The minimum clearances are given in the installation instructions. Also allow for working space in front of filters, control panels and shut-off valves so that maintenance remains possible without removing other devices.
Conclusion
It pays to plan the plant room early, as later changes are expensive. Make a list of all devices, check floor space and maintenance clearances in the data sheets and, in a detached house, expect closer to 10 than 6 square metres. Short distances to the external wall, distance from bedrooms, a floor drain and consistent insulation of all pipes make the room practical in the long term. Anyone planning a plant room should also allow spare space for future technology. Clarify the refrigerant and utility connection in good time with the manufacturer and network operator. You will find components for your plant room in our Ventilation Systems and Heat Pumps categories.