Description
S&P CAIT PRO-REG: Supply Air Unit, Electric Heating Coil. Available are 33 versions as well as 10 sizes as well as the orientations left and right.
Technical data
Technical data
| Manufacturer | S&P |
|---|---|
| Coil design | heating elements made of stainless steel (AISI 430), two safety thermostats (55 °C automatic reset, 85 °C manual reset), proportional control via static relay for the first stage, sequencing of the further stages |
| Building management | Modbus RTU (RS485), BACnet TCP/IP, web server TCP/IP |
| Insulation | mineral wool 50 mm (40 kg/m³, thermal conductivity 0.037 W/(m·K)), non-combustible (A1 according to EN 13501-1) |
| Operating temperature | -25 to +40 °C |
| Control | PRO-REG, integrated |
| S&P type | Item number | Version | Size | Orientation | Max. airflow | Heating output | Total power | Total current | Weight | Series | Coil | Operating side (in supply air direction) | Power supply |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CAIT-48 M5 E9 PRO-REG L | 5209369700 | CAIT M5 E9 PRO-REG | 48 | left | 5,000 m³/h | 9 kW | 11 kW | 15 A | 278 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-48 M5 E9 PRO-REG R | 5209364400 | CAIT M5 E9 PRO-REG | 48 | right | 5,000 m³/h | 9 kW | 11 kW | 15 A | 278 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-48 M5 E9 PRO-REG L OI | 5209367000 | CAIT M5 E9 PRO-REG OI | 48 | left | 5,000 m³/h | 9 kW | 11 kW | 15 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-48 M5 E9 PRO-REG R OI | 5209361700 | CAIT M5 E9 PRO-REG OI | 48 | right | 5,000 m³/h | 9 kW | 11 kW | 15 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-48 M5 E27 PRO-REG L | 5209369600 | CAIT M5 E27 PRO-REG | 48 | left | 5,000 m³/h | 27 kW | 30 kW | 43 A | 278 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-48 M5 E27 PRO-REG R | 5209364300 | CAIT M5 E27 PRO-REG | 48 | right | 5,000 m³/h | 27 kW | 30 kW | 43 A | 278 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-48 M5 E27 PRO-REG L OI | 5209366900 | CAIT M5 E27 PRO-REG OI | 48 | left | 5,000 m³/h | 27 kW | 30 kW | 43 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-48 M5 E27 PRO-REG R OI | 5209361600 | CAIT M5 E27 PRO-REG OI | 48 | right | 5,000 m³/h | 27 kW | 30 kW | 43 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-88 M5 E30 PRO-REG L | 5209370000 | CAIT M5 E30 PRO-REG | 88 | left | 9,000 m³/h | 30 kW | 34 kW | 50 A | 417 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-88 M5 E30 PRO-REG R | 5209364700 | CAIT M5 E30 PRO-REG | 88 | right | 9,000 m³/h | 30 kW | 34 kW | 50 A | 417 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-88 M5 E30 PRO-REG L OI | 5209367300 | CAIT M5 E30 PRO-REG OI | 88 | left | 9,000 m³/h | 30 kW | 34 kW | 50 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-88 M5 E30 PRO-REG R OI | 5209362000 | CAIT M5 E30 PRO-REG OI | 88 | right | 9,000 m³/h | 30 kW | 34 kW | 50 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-48 M5 E45 PRO-REG L | 5209369500 | CAIT M5 E45 PRO-REG | 48 | left | 5,000 m³/h | 45 kW | 48 kW | 70 A | 278 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-48 M5 E45 PRO-REG R | 5209364200 | CAIT M5 E45 PRO-REG | 48 | right | 5,000 m³/h | 45 kW | 48 kW | 70 A | 278 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-120 M5 E45 PRO-REG ID L | 5209370600 | CAIT M5 E45 PRO-REG ID | 120 | left | 12,000 m³/h | 45 kW | 53 kW | 78 A | 696 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-120 M5 E45 PRO-REG ID R | 5209365300 | CAIT M5 E45 PRO-REG ID | 120 | right | 12,000 m³/h | 45 kW | 53 kW | 78 A | 696 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-120 M5 E45 PRO-REG ID L OI | 5209367900 | CAIT M5 E45 PRO-REG ID OI | 120 | left | 12,000 m³/h | 45 kW | 53 kW | 78 A | not specified | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | left | 3/400 V, 50 Hz |
| CAIT-120 M5 E45 PRO-REG ID R OI | 5209362600 | CAIT M5 E45 PRO-REG ID OI | 120 | right | 12,000 m³/h | 45 kW | 53 kW | 78 A | not specified | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | right | 3/400 V, 50 Hz |
| CAIT-48 M5 E45 PRO-REG L OI | 5209366800 | CAIT M5 E45 PRO-REG OI | 48 | left | 5,000 m³/h | 45 kW | 48 kW | 70 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-48 M5 E45 PRO-REG R OI | 5209361500 | CAIT M5 E45 PRO-REG OI | 48 | right | 5,000 m³/h | 45 kW | 48 kW | 70 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-88 M5 E60 PRO-REG L | 5209369900 | CAIT M5 E60 PRO-REG | 88 | left | 9,000 m³/h | 60 kW | 66 kW | 95 A | 417 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-88 M5 E60 PRO-REG R | 5209364600 | CAIT M5 E60 PRO-REG | 88 | right | 9,000 m³/h | 60 kW | 66 kW | 95 A | 417 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-88 M5 E60 PRO-REG L OI | 5209367200 | CAIT M5 E60 PRO-REG OI | 88 | left | 9,000 m³/h | 60 kW | 66 kW | 95 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-88 M5 E60 PRO-REG R OI | 5209361900 | CAIT M5 E60 PRO-REG OI | 88 | right | 9,000 m³/h | 60 kW | 66 kW | 95 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-120 M5 E75 PRO-REG ID L | 5209370500 | CAIT M5 E75 PRO-REG ID | 120 | left | 12,000 m³/h | 75 kW | 85 kW | 123 A | 696 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-120 M5 E75 PRO-REG ID R | 5209365200 | CAIT M5 E75 PRO-REG ID | 120 | right | 12,000 m³/h | 75 kW | 85 kW | 123 A | 696 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-160 M5 E75 PRO-REG ID L | 5209053100 | CAIT M5 E75 PRO-REG ID | 160 | left | 16,000 m³/h | 75 kW | 80 kW | 116 A | 823 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-160 M5 E75 PRO-REG ID R | 5209051800 | CAIT M5 E75 PRO-REG ID | 160 | right | 16,000 m³/h | 75 kW | 80 kW | 116 A | 823 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-120 M5 E75 PRO-REG ID L OI | 5209367800 | CAIT M5 E75 PRO-REG ID OI | 120 | left | 12,000 m³/h | 75 kW | 85 kW | 123 A | not specified | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | left | 3/400 V, 50 Hz |
| CAIT-120 M5 E75 PRO-REG ID R OI | 5209362500 | CAIT M5 E75 PRO-REG ID OI | 120 | right | 12,000 m³/h | 75 kW | 85 kW | 123 A | not specified | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | right | 3/400 V, 50 Hz |
| CAIT-160 M5 E75 PRO-REG ID L OI | 5209052600 | CAIT M5 E75 PRO-REG ID OI | 160 | left | 16,000 m³/h | 75 kW | 80 kW | 116 A | 882 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | left | 3/400 V, 50 Hz |
| CAIT-160 M5 E75 PRO-REG ID R OI | 5209052200 | CAIT M5 E75 PRO-REG ID OI | 160 | right | 16,000 m³/h | 75 kW | 80 kW | 116 A | 882 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | right | 3/400 V, 50 Hz |
| CAIT-88 M5 E90 PRO-REG L | 5209369800 | CAIT M5 E90 PRO-REG | 88 | left | 9,000 m³/h | 90 kW | 97 kW | 141 A | 417 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-88 M5 E90 PRO-REG R | 5209364500 | CAIT M5 E90 PRO-REG | 88 | right | 9,000 m³/h | 90 kW | 97 kW | 141 A | 417 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-160 M5 E90 PRO-REG ID L | 5209053200 | CAIT M5 E90 PRO-REG ID | 160 | left | 16,000 m³/h | 90 kW | 95 kW | 138 A | 823 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-160 M5 E90 PRO-REG ID R | 5209051900 | CAIT M5 E90 PRO-REG ID | 160 | right | 16,000 m³/h | 90 kW | 95 kW | 138 A | 823 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-200 M5 E90 PRO-REG ID L | 5209055000 | CAIT M5 E90 PRO-REG ID | 200 | left | 20,000 m³/h | 90 kW | 101 kW | 146 A | 1078 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-200 M5 E90 PRO-REG ID R | 5209053600 | CAIT M5 E90 PRO-REG ID | 200 | right | 20,000 m³/h | 90 kW | 101 kW | 146 A | 1078 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-160 M5 E90 PRO-REG ID L OI | 5209052700 | CAIT M5 E90 PRO-REG ID OI | 160 | left | 16,000 m³/h | 90 kW | 95 kW | 138 A | 882 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | left | 3/400 V, 50 Hz |
| CAIT-160 M5 E90 PRO-REG ID R OI | 5209052300 | CAIT M5 E90 PRO-REG ID OI | 160 | right | 16,000 m³/h | 90 kW | 95 kW | 138 A | 882 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | right | 3/400 V, 50 Hz |
| CAIT-200 M5 E90 PRO-REG ID L OI | 5209054600 | CAIT M5 E90 PRO-REG ID OI | 200 | left | 20,000 m³/h | 90 kW | 101 kW | 146 A | 1144 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | left | 3/400 V, 50 Hz |
| CAIT-200 M5 E90 PRO-REG ID R OI | 5209054100 | CAIT M5 E90 PRO-REG ID OI | 200 | right | 20,000 m³/h | 90 kW | 101 kW | 146 A | 1144 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | right | 3/400 V, 50 Hz |
| CAIT-88 M5 E90 PRO-REG L OI | 5209367100 | CAIT M5 E90 PRO-REG OI | 88 | left | 9,000 m³/h | 90 kW | 97 kW | 141 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | left | 3/400 V, 50 Hz |
| CAIT-88 M5 E90 PRO-REG R OI | 5209361800 | CAIT M5 E90 PRO-REG OI | 88 | right | 9,000 m³/h | 90 kW | 97 kW | 141 A | n/a | CAIT-48 to 200 PRO-REG | electric heating coil (E9, E27, E30, E45, E60, E90) | right | 3/400 V, 50 Hz |
| CAIT-120 M5 E105 PRO-REG ID L | 5209370400 | CAIT M5 E105 PRO-REG ID | 120 | left | 12,000 m³/h | 105 kW | 116 kW | 169 A | 696 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-120 M5 E105 PRO-REG ID R | 5209365100 | CAIT M5 E105 PRO-REG ID | 120 | right | 12,000 m³/h | 105 kW | 116 kW | 169 A | 696 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-120 M5 E105 PRO-REG ID L OI | 5209367700 | CAIT M5 E105 PRO-REG ID OI | 120 | left | 12,000 m³/h | 105 kW | 116 kW | 169 A | not specified | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | left | 3/400 V, 50 Hz |
| CAIT-120 M5 E105 PRO-REG ID R OI | 5209362400 | CAIT M5 E105 PRO-REG ID OI | 120 | right | 12,000 m³/h | 105 kW | 116 kW | 169 A | not specified | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105) | right | 3/400 V, 50 Hz |
| CAIT-160 M5 E120 PRO-REG ID L | 5209052800 | CAIT M5 E120 PRO-REG ID | 160 | left | 16,000 m³/h | 120 kW | 125 kW | 181 A | 823 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-160 M5 E120 PRO-REG ID R | 5209051600 | CAIT M5 E120 PRO-REG ID | 160 | right | 16,000 m³/h | 120 kW | 125 kW | 181 A | 823 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-200 M5 E120 PRO-REG ID L | 5209054700 | CAIT M5 E120 PRO-REG ID | 200 | left | 20,000 m³/h | 120 kW | 131 kW | 189 A | 1078 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-200 M5 E120 PRO-REG ID R | 5209053300 | CAIT M5 E120 PRO-REG ID | 200 | right | 20,000 m³/h | 120 kW | 131 kW | 189 A | 1078 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-160 M5 E120 PRO-REG ID L OI | 5209052400 | CAIT M5 E120 PRO-REG ID OI | 160 | left | 16,000 m³/h | 120 kW | 125 kW | 181 A | 882 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-160 M5 E120 PRO-REG ID R OI | 5209052000 | CAIT M5 E120 PRO-REG ID OI | 160 | right | 16,000 m³/h | 120 kW | 125 kW | 181 A | 882 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-200 M5 E120 PRO-REG ID L OI | 5209054200 | CAIT M5 E120 PRO-REG ID OI | 200 | left | 20,000 m³/h | 120 kW | 131 kW | 189 A | 1144 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-200 M5 E120 PRO-REG ID R OI | 5209053800 | CAIT M5 E120 PRO-REG ID OI | 200 | right | 20,000 m³/h | 120 kW | 131 kW | 189 A | 1144 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-160 M5 E150 PRO-REG ID L | 5209053000 | CAIT M5 E150 PRO-REG ID | 160 | left | 16,000 m³/h | 150 kW | 155 kW | 224 A | 823 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-160 M5 E150 PRO-REG ID R | 5209051700 | CAIT M5 E150 PRO-REG ID | 160 | right | 16,000 m³/h | 150 kW | 155 kW | 224 A | 823 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-200 M5 E150 PRO-REG ID L | 5209054800 | CAIT M5 E150 PRO-REG ID | 200 | left | 20,000 m³/h | 150 kW | 161 kW | 233 A | 1078 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-200 M5 E150 PRO-REG ID R | 5209053400 | CAIT M5 E150 PRO-REG ID | 200 | right | 20,000 m³/h | 150 kW | 161 kW | 233 A | 1078 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-160 M5 E150 PRO-REG ID L OI | 5209052500 | CAIT M5 E150 PRO-REG ID OI | 160 | left | 16,000 m³/h | 150 kW | 155 kW | 224 A | 882 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-160 M5 E150 PRO-REG ID R OI | 5209052100 | CAIT M5 E150 PRO-REG ID OI | 160 | right | 16,000 m³/h | 150 kW | 155 kW | 224 A | 882 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-200 M5 E150 PRO-REG ID L OI | 5209054300 | CAIT M5 E150 PRO-REG ID OI | 200 | left | 20,000 m³/h | 150 kW | 161 kW | 233 A | 1144 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-200 M5 E150 PRO-REG ID R OI | 5209053900 | CAIT M5 E150 PRO-REG ID OI | 200 | right | 20,000 m³/h | 150 kW | 161 kW | 233 A | 1144 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-200 M5 E165 PRO-REG ID L | 5209054900 | CAIT M5 E165 PRO-REG ID | 200 | left | 20,000 m³/h | 165 kW | 176 kW | 254 A | 1078 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-200 M5 E165 PRO-REG ID R | 5209053500 | CAIT M5 E165 PRO-REG ID | 200 | right | 20,000 m³/h | 165 kW | 176 kW | 254 A | 1078 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E45, E75, E90, E105, E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-200 M5 E165 PRO-REG ID L OI | 5209054400 | CAIT M5 E165 PRO-REG ID OI | 200 | left | 20,000 m³/h | 165 kW | 176 kW | 254 A | 1144 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | left | 3/400 V, 50 Hz |
| CAIT-200 M5 E165 PRO-REG ID R OI | 5209054000 | CAIT M5 E165 PRO-REG ID OI | 200 | right | 20,000 m³/h | 165 kW | 176 kW | 254 A | 1144 kg | CAIT-48 to 200 PRO-REG | electric heating coil (E120, E150, E165) | right | 3/400 V, 50 Hz |
| CAIT-10 M5 F7 E9 PRO-REG L | 5209381400 | CAIT M5 F7 E9 PRO-REG | 10 | left | 1,000 m³/h | 9 kW | 10 kW | 15 A | 55 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-10 M5 F7 E9 PRO-REG R | 5209381200 | CAIT M5 F7 E9 PRO-REG | 10 | right | 1,000 m³/h | 9 kW | 10 kW | 15 A | 55 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-20 M5 F7 E9 PRO-REG L | 5209381800 | CAIT M5 F7 E9 PRO-REG | 20 | left | 2,000 m³/h | 9 kW | 10 kW | 16 A | 99 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-20 M5 F7 E9 PRO-REG R | 5209381600 | CAIT M5 F7 E9 PRO-REG | 20 | right | 2,000 m³/h | 9 kW | 10 kW | 16 A | 99 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-30 M5 F7 E9 PRO-REG L | 5209382300 | CAIT M5 F7 E9 PRO-REG | 30 | left | 3,000 m³/h | 9 kW | 10 kW | 17 A | 103 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-30 M5 F7 E9 PRO-REG R | 5209382100 | CAIT M5 F7 E9 PRO-REG | 30 | right | 3,000 m³/h | 9 kW | 10 kW | 17 A | 103 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-50 M5 F7 E12 PRO-REG L | 5209075800 | CAIT M5 F7 E12 PRO-REG | 50 | left | 5,000 m³/h | 12 kW | 14 kW | 21 A | see data sheet | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-50 M5 F7 E12 PRO-REG R | 5209075100 | CAIT M5 F7 E12 PRO-REG | 50 | right | 5,000 m³/h | 12 kW | 14 kW | 21 A | see data sheet | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-20 M5 F7 E15 PRO-REG L | 5209381700 | CAIT M5 F7 E15 PRO-REG | 20 | left | 2,000 m³/h | 15 kW | 16 kW | 25 A | 99 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-20 M5 F7 E15 PRO-REG R | 5209381500 | CAIT M5 F7 E15 PRO-REG | 20 | right | 2,000 m³/h | 15 kW | 16 kW | 25 A | 99 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-30 M5 F7 E15 PRO-REG L | 5209382400 | CAIT M5 F7 E15 PRO-REG | 30 | left | 3,000 m³/h | 15 kW | 17 kW | 26 A | 103 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-30 M5 F7 E15 PRO-REG R | 5209381900 | CAIT M5 F7 E15 PRO-REG | 30 | right | 3,000 m³/h | 15 kW | 17 kW | 26 A | 103 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-40 M5 F7 E15 PRO-REG L | 5209382700 | CAIT M5 F7 E15 PRO-REG | 40 | left | 4,000 m³/h | 15 kW | 17 kW | 24 A | 112 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-40 M5 F7 E15 PRO-REG R | 5209382500 | CAIT M5 F7 E15 PRO-REG | 40 | right | 4,000 m³/h | 15 kW | 17 kW | 24 A | 112 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-30 M5 F7 E24 PRO-REG L | 5209382200 | CAIT M5 F7 E24 PRO-REG | 30 | left | 3,000 m³/h | 24 kW | 26 kW | 40 A | 103 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-30 M5 F7 E24 PRO-REG R | 5209382000 | CAIT M5 F7 E24 PRO-REG | 30 | right | 3,000 m³/h | 24 kW | 26 kW | 40 A | 103 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-50 M5 F7 E24 PRO-REG L | 5209075900 | CAIT M5 F7 E24 PRO-REG | 50 | left | 5,000 m³/h | 24 kW | 26 kW | 38 A | see data sheet | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-50 M5 F7 E24 PRO-REG R | 5209075200 | CAIT M5 F7 E24 PRO-REG | 50 | right | 5,000 m³/h | 24 kW | 26 kW | 38 A | see data sheet | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-40 M5 F7 E30 PRO-REG L | 5209382800 | CAIT M5 F7 E30 PRO-REG | 40 | left | 4,000 m³/h | 30 kW | 33 kW | 47 A | 112 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-40 M5 F7 E30 PRO-REG R | 5209382600 | CAIT M5 F7 E30 PRO-REG | 40 | right | 4,000 m³/h | 30 kW | 33 kW | 47 A | 112 kg | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-50 M5 F7 E36 PRO-REG L | 5209076000 | CAIT M5 F7 E36 PRO-REG | 50 | left | 5,000 m³/h | 36 kW | 38 kW | 55 A | see data sheet | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-50 M5 F7 E36 PRO-REG R | 5209075300 | CAIT M5 F7 E36 PRO-REG | 50 | right | 5,000 m³/h | 36 kW | 38 kW | 55 A | see data sheet | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
| CAIT-50 M5 F7 E48 PRO-REG L | 5209076100 | CAIT M5 F7 E48 PRO-REG | 50 | left | 5,000 m³/h | 48 kW | 50 kW | 73 A | see data sheet | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | left | 3+N/400 V, 50 Hz |
| CAIT-50 M5 F7 E48 PRO-REG R | 5209075400 | CAIT M5 F7 E48 PRO-REG | 50 | right | 5,000 m³/h | 48 kW | 50 kW | 73 A | see data sheet | CAIB/CAIT-10 to 50 PRO-REG | electric heating coil (E9, E12, E15, E24, E30, E36, E48) | right | 3+N/400 V, 50 Hz |
Features
Features
- Standard according to the manufacturer: one mains connection point with maintenance switch for the entire unit, outdoor air and supply air temperature sensor, filter monitoring with indication on the display.
- Time control (weekly and holiday program), BOOST function and ON/OFF via external signal; CAV with two-stage operation, VAV according to air quality (carbon dioxide, VOC) or relative humidity via a sensor available as an accessory, COP via a differential pressure transmitter available as an accessory.
- Control of external motorised outdoor air shut-off dampers (24 V); optional extract air or room temperature sensor (TG-K3 PT1000 or TG-R5 PT1000).
Note on variants
Note on variants
The table above lists the S&P type and the item number for each option.
Data sheets and manuals (PDF)
Data sheets and manuals (PDF)
Ask about this product
We usually reply within one business day.
Note on reviews: Any visitor can submit a review using the form; a purchase is not required. Anyone who submits a review receives an email to confirm their email address. Reviews marked “Verified” come from customers who bought the product from us. We do not check other reviews for a purchase.
From our range
Selected products from ventilation, filter and pipe technology.