S&P CRCB/CRCT ECOWATT HL ASR ISO Ventilation Box, EC Motor, DN 400 to 710
● Shipping: Germany €4.99, free from €100; EU €19.99
✓ Quiet operation with the right sizing
✓ Pay by PayPal, card, Klarna or bank transfer
✓ Expert advice on choosing the right unit
For business customers, larger quantities or projects, we will be happy to prepare a quote for you.
The price for this version is available on request. We will be happy to send you a quote.
You can also pay by bank transfer (prepayment). Bank details follow with the order confirmation.
Description
Description
S&P CRCB/CRCT ECOWATT HL ASR ISO Ventilation Box, EC Motor, DN 400 to 710: sound-insulated ventilation box with EC motor and ASR control, as CRCB for 230 V or as CRCT for 400 V. Options under version: CRCB ECOWATT HL ASR ISO, EC, 230 V and CRCT ECOWATT HL ASR ISO, EC, 400 V.
The versions in detail
The versions in detail
CRCB ECOWATT HL ASR ISO, EC, 230 V: S&P CRCB ECOWATT HL ASR ISO are ventilation boxes with EC motor for commercial kitchens and industrial process applications, according to S&P only in combination with supply air units of the CAIB/CAIT PRO-REG series. The motors are separated from the air flow and externally ventilated. According to S&P, the ASR system allows a jointly controlled supply and extract air system for commercial kitchens: parameterisation of supply and extract air (also with unequal volumes, e.g. negative pressure), display and adjustment of the air flow, supply air temperature control as well as comfort and smoke extraction mode.
CRCT ECOWATT HL ASR ISO, EC, 400 V: S&P CRCT ECOWATT 92-HL ASR ISO is a sound-insulated ventilation box with EC motor for commercial kitchens and industrial process applications. According to S&P, it can only be used in combination with supply air units of the CAIB / CAIT PRO-REG series (ASR system for jointly controlled supply and exhaust air). The motor is separated from the air flow and externally ventilated; the backward-curved centrifugal impeller is equipped with an EC external rotor motor.
Technical data
Technical data
Data per version:
| Feature | CRCB ECOWATT HL ASR ISO, EC, 230 V | CRCT ECOWATT HL ASR ISO, EC, 400 V |
|---|---|---|
| Power supply | 1~ 230 V, 50/60 Hz | 3~ 400 V, 50/60 Hz |
| Impeller | backward-curved centrifugal impeller | not specified |
| Motor | EC external rotor motor, insulation class F, protection rating IP 55, internal thermal contacts, continuous operation S1, sealed ball bearings | EC, thermal class F, protection rating IP55, internal thermal contacts |
| Speed control | 0 to 100 % via 0-10 V signal | not specified |
| Medium temperature | -20 °C to 120 °C | -20 to 120 °C |
| Housing | self-supporting, galvanised sheet steel, 25 mm acoustic lining, non-combustible (M0) | not specified |
| Type | not specified | CRCT ECOWATT 92-HL ASR ISO |
| Nominal size | not specified | 710 mm |
| Max. speed | not specified | 1,500 rpm |
| Max. power consumption | not specified | 1,700 W |
| Max. motor current | not specified | 3.5 A |
| Air flow (free blowing) | not specified | 9,200 m³/h |
| Sound pressure level inlet / outlet side | not specified | 83 / 76 dB(A) |
| Weight | not specified | 171 kg |
| Control | not specified | 0 to 100% via 0-10 V signal |
Note on variants
Note on variants
Select version and size. Not every combination is available.
| Version | Size | Item number | Nominal size | Speed | Max. power | Motor current | Free-blowing air flow | Sound pressure inlet/outlet | Weight |
|---|---|---|---|---|---|---|---|---|---|
| CRCB ECOWATT HL ASR ISO, EC, 230 V | 30-HL, DN 400 | 5209060000 | 400 mm | 2,250 rpm | 600 W | 2.6 A | 3,000 m³/h | 78 / 71 dB(A) | 64 kg |
| CRCB ECOWATT HL ASR ISO, EC, 230 V | 38-HL, DN 500 | 5209060100 | 500 mm | 1,830 rpm | 700 W | 3.1 A | 3,800 m³/h | 79 / 72 dB(A) | 78 kg |
| CRCB ECOWATT HL ASR ISO, EC, 230 V | 48-HL, DN 560 | 5209060300 | 560 mm | 1,500 rpm | 720 W | 3.1 A | 5,000 m³/h | 78 / 71 dB(A) | 107 kg |
| CRCB ECOWATT HL ASR ISO, EC, 230 V | 70-HL, DN 630 | 5209060400 | 630 mm | 1,500 rpm | 1,240 W | 5.4 A | 7,000 m³/h | 81 / 76 dB(A) | 121 kg |
| CRCB ECOWATT HL ASR ISO, EC, 230 V | 82-HL, DN 710 | 5209060500 | 710 mm | 1,350 rpm | 1,400 W | 6.0 A | 8,200 m³/h | 81 / 75 dB(A) | 170 kg |
| CRCT ECOWATT HL ASR ISO, EC, 400 V | 92-HL, DN 710 | 5209061100 | 710 mm | 171 kg |
Features
Features
- Inspection opening can be opened without tools, with handles.
- CRCB ECOWATT HL ASR ISO, EC, 230 V: Condensate drain spigot supplied loose, fitted depending on installation.
- Terminal box with maintenance switch.
- CRCB ECOWATT HL ASR ISO, EC, 230 V: Accessories according to S&P: APC discharge spigot (400, 500), KAA flexible connectors, KSE anti-vibration mounts, WKS-1040 wall bracket set (30-HL to 70-HL).
- CRCT ECOWATT HL ASR ISO, EC, 400 V: Self-supporting housing made of galvanised sheet steel with 25 mm sound insulation lining, non-combustible (M0).
- CRCT ECOWATT HL ASR ISO, EC, 400 V: Condensate drain spigot supplied loose.
- CRCT ECOWATT HL ASR ISO, EC, 400 V: ASR system according to S&P: parameterisation of supply and exhaust air, display and adjustment of the air flow, supply air temperature control, comfort and smoke extraction mode.
- CRCT ECOWATT HL ASR ISO, EC, 400 V: Performance data according to S&P to ISO 5801.
Ask about this product
We usually reply within one business day.
Note on reviews: Any visitor can submit a review using the form; a purchase is not required. Anyone who submits a review receives an email to confirm their email address. Reviews marked “Verified” come from customers who bought the product from us. We do not check other reviews for a purchase.
From our range
Selected products from ventilation, filter and pipe technology.