S&P SLIM: Low-Profile Ventilation Unit. Available are the versions SLIM and SLIM PH as well as the sizes 800, 1200, 1600, 2000 and 2400 as well as the orientations left and right.
Technical data
Technical data
| Manufacturer | S&P |
|---|---|
| Heat exchanger | counterflow, aluminium, EUROVENT certified according to the manufacturer |
| Bypass | integrated (100%), for free cooling, free heating and icing protection |
| Fans | backward curved impellers with EC motor, access from below |
| Filters | extract air M5 (ePM10 ≥ 50%), supply air F7 (ePM1 ≥ 70%); F9 (ePM1 ≥ 85%) available as an accessory on request; filter monitoring via integrated differential pressure measurement |
| Housing | self-supporting, double-walled, aluminium profiles; side panels made of galvanised sheet steel on the outside and inside; maintenance access via sliding doors on the underside |
| Insulation | mineral wool 30 mm (100 kg/m³, thermal conductivity 0.037 W/(m·K)), non-combustible (A1/M0) |
| Condensate | integrated condensate pump, side condensate connection (1/2") |
| Control | integrated, preconfigured (plug & play), controller and terminal box in a separate housing on the operating side |
| Operation | touch display, included |
| Building management | Modbus RTU (RS485), BACnet TCP/IP, web server |
| Series | SLIM |
| Air connections | side, horizontal; rectangular duct connections without flange |
| S&P type | Item number | Version | Size | Orientation | Nominal airflow | Connection size | Heat recovery efficiency² | Power supply | Current | Dimensions (A x B x C) | Weight | Sound pressure, casing³ | Pre-heater |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SLIM 800 L | 5153137100 | SLIM | 800 | left | 800 m³/h | 400 x 200 mm | 92.4% | 1/230 V, 50 Hz | 2.9 A | 1700 x 1080 x 380 mm | 172 kg | 48 dB(A) | not included, can be retrofitted (SL-PH) |
| SLIM 800 R | 5153137300 | SLIM | 800 | right | 800 m³/h | 400 x 200 mm | 92.4% | 1/230 V, 50 Hz | 2.9 A | 1700 x 1080 x 380 mm | 172 kg | 48 dB(A) | not included, can be retrofitted (SL-PH) |
| SLIM 1200 L | 5153137500 | SLIM | 1200 | left | 1,200 m³/h | 500 x 250 mm | 92.4% | 1/230 V, 50 Hz | 4.1 A | 1700 x 1560 x 380 mm | 231 kg | 49 dB(A) | not included, can be retrofitted (SL-PH) |
| SLIM 1200 R | 5153137700 | SLIM | 1200 | right | 1,200 m³/h | 500 x 250 mm | 92.4% | 1/230 V, 50 Hz | 4.1 A | 1700 x 1560 x 380 mm | 231 kg | 49 dB(A) | not included, can be retrofitted (SL-PH) |
| SLIM 1600 L | 5153137900 | SLIM | 1600 | left | 1,600 m³/h | 600 x 300 mm | 91.7% | 1/230 V, 50 Hz | 3.7 A | 1700 x 1760 x 420 mm | 266 kg | 51 dB(A) | not included, can be retrofitted (SL-PH) |
| SLIM 1600 R | 5153138100 | SLIM | 1600 | right | 1,600 m³/h | 600 x 300 mm | 91.7% | 1/230 V, 50 Hz | 3.7 A | 1700 x 1760 x 420 mm | 266 kg | 51 dB(A) | not included, can be retrofitted (SL-PH) |
| SLIM 2000 L | 5153138300 | SLIM | 2000 | left | 2,000 m³/h | 600 x 350 mm | 93.8% | 1/230 V, 50 Hz | 4.5 A | 2000 x 1760 x 500 mm | 315 kg | 44 dB(A) | not included, can be retrofitted (SL-PH) |
| SLIM 2000 R | 5153138500 | SLIM | 2000 | right | 2,000 m³/h | 600 x 350 mm | 93.8% | 1/230 V, 50 Hz | 4.5 A | 2000 x 1760 x 500 mm | 315 kg | 44 dB(A) | not included, can be retrofitted (SL-PH) |
| SLIM 2400 L | 5153207700 | SLIM | 2400 | left | 2,400 m³/h | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not included, can be retrofitted (SL-PH) |
| SLIM 2400 R | 5153207900 | SLIM | 2400 | right | 2,400 m³/h | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not included, can be retrofitted (SL-PH) |
| SLIM 800 PH L | 5153137200 | SLIM PH | 800 | left | 800 m³/h | 400 x 200 mm | 92.4% | 1/230 V, 50 Hz | 12.9 A | 1700 x 1080 x 380 mm | 176 kg | 48 dB(A) | 2.2 kW |
| SLIM 800 PH R | 5153137400 | SLIM PH | 800 | right | 800 m³/h | 400 x 200 mm | 92.4% | 1/230 V, 50 Hz | 12.9 A | 1700 x 1080 x 380 mm | 176 kg | 48 dB(A) | 2.2 kW |
| SLIM 1200 PH L | 5153137600 | SLIM PH | 1200 | left | 1,200 m³/h | 500 x 250 mm | 92.4% | 1/230 V, 50 Hz | 17.8 A | 1700 x 1560 x 380 mm | 236 kg | 49 dB(A) | 3 kW |
| SLIM 1200 PH R | 5153137800 | SLIM PH | 1200 | right | 1,200 m³/h | 500 x 250 mm | 92.4% | 1/230 V, 50 Hz | 17.8 A | 1700 x 1560 x 380 mm | 236 kg | 49 dB(A) | 3 kW |
| SLIM 1600 PH L | 5153138000 | SLIM PH | 1600 | left | 1,600 m³/h | 600 x 300 mm | 91.7% | 3/400 V + N, 50 Hz | 12.8 A | 1700 x 1760 x 420 mm | 273 kg | 51 dB(A) | 6 kW |
| SLIM 1600 PH R | 5153138200 | SLIM PH | 1600 | right | 1,600 m³/h | 600 x 300 mm | 91.7% | 3/400 V + N, 50 Hz | 12.8 A | 1700 x 1760 x 420 mm | 273 kg | 51 dB(A) | 6 kW |
| SLIM 2000 PH L | 5153138400 | SLIM PH | 2000 | left | 2,000 m³/h | 600 x 350 mm | 93.8% | 3/400 V + N, 50 Hz | 15.9 A | 2000 x 1760 x 500 mm | 323 kg | 44 dB(A) | 7.5 kW |
| SLIM 2000 PH R | 5153138600 | SLIM PH | 2000 | right | 2,000 m³/h | 600 x 350 mm | 93.8% | 3/400 V + N, 50 Hz | 15.9 A | 2000 x 1760 x 500 mm | 323 kg | 44 dB(A) | 7.5 kW |
| SLIM 2400 PH L | 5153207800 | SLIM PH | 2400 | left | 2,400 m³/h | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ |
| SLIM 2400 PH R | 5153208000 | SLIM PH | 2400 | right | 2,400 m³/h | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ | not specified¹ |
Features
Features
- Standard according to the manufacturer: one mains connection point with maintenance switch for the entire unit; all sensors required for operation are pre-installed and connected (outdoor air, supply air, extract air and exhaust air temperature).
- Alarm and monitoring functions: filters, sensors, fans, condensate pump, heat exchanger, fire and smoke alarm, frost protection for water coils, overheating of the electric heating coil, heat recovery efficiency, alarm memory.
- Replacement filters according to the manufacturer: AFR-SLIM filter inserts for the respective size in classes M5, F7 and F9.
Note on variants
Note on variants
The table above lists the S&P type and the item number for each option.
Ask about this product
We usually reply within one business day.
Note on reviews: Any visitor can submit a review using the form; a purchase is not required. Anyone who submits a review receives an email to confirm their email address. Reviews marked “Verified” come from customers who bought the product from us. We do not check other reviews for a purchase.
From our range
Selected products from ventilation, filter and pipe technology.