Free shipping from 100 € within Germany
English
Account WishlistCart
S&P Deutschland GmbH  |  SKU: 5604307900

S&P TCBB/TCBT Axial Fan, 230 V or 400 V, DN 250 to 800

1.61149 € 2.28123 €
Tax included Shipping calculated at checkout.
● Delivery time: 5 to 10 business days
● Shipping: Germany €4.99, free from €100; EU €19.99
✓ Original manufacturer unit, CE marked
✓ Quiet operation with the right sizing
✓ Pay by PayPal, card, Klarna or bank transfer
✓ Expert advice on choosing the right unit
Request a quote

For business customers, larger quantities or projects, we will be happy to prepare a quote for you.

  • American Express
  • Apple Pay
  • Google Pay
  • Klarna
  • Mastercard
  • PayPal
  • Shop Pay
  • Visa
  • Bank transfer

You can also pay by bank transfer (prepayment). Bank details follow with the order confirmation.

Description

S&P TCBB/TCBT Axial Fan, 230 V or 400 V, DN 250 to 800: axial fan in a tubular casing for circular ductwork, as TCBB for single-phase 230 V or as TCBT for three-phase 400 V, with the blade positions H, L, G and K and as high-pressure axial fan TCBBx2/TCBTx2 with two counter-rotating impellers. 15 versions are available under version.

The versions in detail

TCBT H, 400 V: S&P TCBT H is a selection of axial tube fans from the S&P TCBB/TCBT series for three-phase 3~ 400 V with blade pitch H, impeller diameter 250 to 800 mm. The fans have a tubular sheet steel housing with connecting flanges on both sides for installation in ducts; according to S&P they can be operated in any axis position.

TCBT L, 400 V: S&P TCBT L is a selection of axial tube fans from the S&P TCBB/TCBT series for three-phase 3~ 400 V with blade pitch L, impeller diameter 560 to 800 mm. The fans have a tubular sheet steel housing with connecting flanges on both sides for installation in ducts; according to S&P they can be operated in any axis position.

TCBTx2 high pressure, 400 V: S&P TCBTx2 is a selection of high-pressure axial fans from the S&P TCBBX2/TCBTX2 series in contra-rotating design for three-phase 3~ 400 V, impeller diameter 450 to 630 mm. According to S&P, two complementary contra-rotating impellers double the pressure at the same airflow. The fans have a tubular sheet steel housing with connecting flanges on both sides for installation in ducts and, according to S&P, can be operated in any axis position.

TCBT H-B, 400 V: S&P TCBT/4-250/H-B is an axial tube fan from the S&P TCBB/TCBT series for three-phase 3~ 400 V with impeller diameter 250 mm, 4-pole motor and blade pitch H. According to the S&P type code, the suffix B stands for the standard air direction B (impeller over motor). The fan has a tubular sheet steel housing with connecting flanges on both sides for installation in ducts; according to S&P it can be operated in any axis position.

TCBT G, 400 V: S&P TCBT/4-800/G is an axial tube fan from the S&P TCBB/TCBT series for three-phase 3~ 400 V with impeller diameter 800 mm and blade pitch G. The fan has a tubular sheet steel housing with connecting flanges on both sides for installation in ducts and a standard motor with PTC thermistor; according to S&P it can be operated in any axis position.

TCBT K, 400 V: S&P TCBT/4-800/K is an axial tube fan from the S&P TCBB/TCBT series for three-phase 3~ 400 V with impeller diameter 800 mm and blade pitch K. The fan has a tubular sheet steel housing with connecting flanges on both sides for installation in ducts and a standard motor with PTC thermistor; according to S&P it can be operated in any axis position.

TCBB H, 230 V: S&P TCBB H is a selection of axial tube fans from the S&P TCBB/TCBT series for single-phase 1~ 230 V with blade pitch H, impeller diameter 250 to 560 mm. The fans have a tubular sheet steel housing with connecting flanges on both sides for installation in ducts; according to S&P they can be operated in any axis position.

TCBB L, 230 V: S&P TCBB L is a selection of axial tube fans from the S&P TCBB/TCBT series for single-phase 1~ 230 V with blade pitch L, impeller diameter 560 to 710 mm. The fans have a tubular sheet steel housing with connecting flanges on both sides for installation in ducts; according to S&P they can be operated in any axis position.

TCBBx2 high pressure, 230 V: S&P TCBBx2 is a selection of high-pressure axial fans from the S&P TCBBX2/TCBTX2 series in contra-rotating design for single-phase 1~ 230 V, impeller diameter 450 and 500 mm. According to S&P, two complementary contra-rotating impellers double the pressure at the same airflow. The fans have a tubular sheet steel housing with connecting flanges on both sides for installation in ducts and, according to S&P, can be operated in any axis position.

Technical data

Housing tubular housing made of sheet steel with connecting flange on both sides, entire construction with epoxy polyester coating, stainless steel screws, terminal box on the housing with PG-11 cable gland
Mounting position any axis position

Data per version:

Feature TCBT H, 400 V TCBT L, 400 V TCBTx2 high pressure, 400 V TCBT H-B, 400 V TCBT G, 400 V TCBT K, 400 V TCBB H, 230 V TCBB L, 230 V TCBBx2 high pressure, 230 V
Series TCBB / TCBT, axial tube fans with pipe flange TCBB / TCBT, axial tube fans with pipe flange TCBBX2 / TCBTX2, high-pressure axial fans with pipe flange, contra-rotating TCBB / TCBT, axial tube fans with pipe flange TCBB / TCBT, axial tube fans with pipe flange TCBB / TCBT, axial tube fans with pipe flange TCBB / TCBT, axial tube fans with pipe flange TCBB / TCBT, axial tube fans with pipe flange TCBBX2 / TCBTX2, high-pressure axial fans with pipe flange, contra-rotating
Mains connection 3~ 400 V, 50 Hz 3~ 400 V, 50 Hz 3~ 400 V, 50 Hz, 4-pole 3~ 400 V, 50 Hz 3~ 400 V, 50 Hz 3~ 400 V, 50 Hz 1~ 230 V, 50 Hz, capacitor motor 1~ 230 V, 50 Hz, capacitor motor 1~ 230 V, 50 Hz, capacitor motor, 4-pole
Impeller axial impeller, statically and dynamically balanced according to ISO 1940; sizes 250, 315, 4-355 and 4-400: sheet steel with epoxy polyester coating; all other models: die-cast aluminium axial impeller, statically and dynamically balanced according to ISO 1940; die-cast aluminium not specified axial impeller, statically and dynamically balanced according to ISO 1940; sizes 250, 315, 4-355 and 4-400: sheet steel with epoxy polyester coating axial impeller, statically and dynamically balanced according to ISO 1940; die-cast aluminium axial impeller, statically and dynamically balanced according to ISO 1940; die-cast aluminium axial impeller, statically and dynamically balanced according to ISO 1940; sizes 250, 315, 4-355 and 4-400: sheet steel with epoxy polyester coating; all other models: die-cast aluminium axial impeller, statically and dynamically balanced according to ISO 1940; die-cast aluminium not specified
Motor AC motor, insulation class F, continuous duty S1, sealed maintenance-free ball bearings; sizes 250, 315, 4-355 and 4-400: protection class IP54, thermal contacts with manual reset according to EN 60335-2-80; other models: protection class IP65 with thermal contact routed separately to the terminal board; sizes 4-710 and 800: protection class IP55, standard motor with PTC thermistor AC motor, insulation class F, continuous duty S1, sealed maintenance-free ball bearings; other models: protection class IP65 with thermal contact routed separately to the terminal board; sizes 4-710 and 800: protection class IP55, standard motor with PTC thermistor not specified AC motor, insulation class F, continuous duty S1, sealed maintenance-free ball bearings; sizes 250, 315, 4-355 and 4-400: protection class IP54, thermal contacts with manual reset according to EN 60335-2-80 AC motor, insulation class F, continuous duty S1, sealed maintenance-free ball bearings; sizes 4-710 and 800: protection class IP55, standard motor with PTC thermistor AC motor, insulation class F, continuous duty S1, sealed maintenance-free ball bearings; sizes 4-710 and 800: protection class IP55, standard motor with PTC thermistor AC motor, insulation class F, continuous duty S1, sealed maintenance-free ball bearings; sizes 250, 315, 4-355 and 4-400: protection class IP54, thermal contacts with manual reset according to EN 60335-2-80; other models: protection class IP65 with thermal contact routed separately to the terminal board AC motor, insulation class F, continuous duty S1, sealed maintenance-free ball bearings; protection class IP65 with thermal contact routed separately to the terminal board not specified
Air direction B (impeller over motor) B (impeller over motor) not specified B (impeller over motor) B (impeller over motor) B (impeller over motor) B (impeller over motor) B (impeller over motor) not specified
Speed control TCBT: by transformer and via frequency inverter (20 to 50 Hz), exceptions see table TCBT: by transformer and via frequency inverter (20 to 50 Hz), exceptions see table by transformer and via frequency inverter (20 to 50 Hz), exceptions see table TCBT: by transformer and via frequency inverter (20 to 50 Hz), exceptions see table TCBT: by transformer and via frequency inverter (20 to 50 Hz), exceptions see table TCBT: by transformer and via frequency inverter (20 to 50 Hz), exceptions see table TCBB: by transformer and electronically (exceptions see table) TCBB: by transformer and electronically (exceptions see table) by transformer and electronically (exceptions see table)

Note on variants

Select version and size. Not every combination is available.

Version Size Item number Speed Power input Motor current Airflow (free-blowing) Sound pressure level¹ Air temperature uncontrolled / speed-controlled Weight
TCBT/2 H, 400 V 250 5705080000 2775 min⁻¹ 114 W 0.2 A 1,730 m³/h 62 dB(A) -40 to +40 °C / -40 to +40 °C 8.0 kg
TCBT/4 H, 400 V 315 5705080500 1445 min⁻¹ 99 W 0.3 A 1,950 m³/h 51 dB(A) -40 to +40 °C / -40 to +40 °C 11.0 kg
TCBT/4 H, 400 V 355 5705080600 1415 min⁻¹ 117 W 0.3 A 2,470 m³/h 52 dB(A) -40 to +40 °C / -40 to +40 °C 13.2 kg
TCBT/4 H, 400 V 400 5740124300 1410 min⁻¹ 268 W 0.5 A 4,950 m³/h 60 dB(A) -40 to +40 °C / -40 to +40 °C 15.5 kg
TCBT/4 H, 400 V 450 5604285700 1405 min⁻¹ 526 W 1.1 A 6,650 m³/h 63 dB(A) -40 to +70 °C / -40 to +50 °C 21.0 kg
TCBT/4 H, 400 V 500 5603999800 1420 min⁻¹ 641 W 1.5 A 7,590 m³/h 66 dB(A) -40 to +70 °C / -40 to +50 °C 25.0 kg
TCBT/4 H, 400 V 560 5603994600 1390 min⁻¹ 1348 W 2.4 A 13,370 m³/h 69 dB(A) -40 to +70 °C / -40 to +50 °C 34.7 kg
TCBT/4 H, 400 V 630 5604308700 1400 min⁻¹ 1940 W 3.6 A 17,030 m³/h 70 dB(A) -40 to +70 °C / -40 to +50 °C 40.0 kg
TCBT/4 H, 400 V 710 5603928400 1460 min⁻¹ 3441 W 6.1 A 26,420 m³/h 73 dB(A) -40 to +40 °C / -40 to +40 °C 54.0 kg
TCBT/4 H, 400 V 800 5605768400 1475 min⁻¹ 7688 W 13.0 A 42,490 m³/h 78 dB(A) -40 to +40 °C / -40 to +40 °C 89.0 kg
TCBT/6 H, 400 V 355 5604586700 900 min⁻¹ 97 W 0.2 A 2,250 m³/h 47 dB(A) -40 to +70 °C / -40 to +50 °C 13.2 kg
TCBT/6 H, 400 V 400 5605049500 860 min⁻¹ 116 W 0.2 A 2,970 m³/h 49 dB(A) -40 to +70 °C / -40 to +50 °C 15.5 kg
TCBT/6 H, 400 V 450 5604311100 940 min⁻¹ 161 W 0.4 A 4,020 m³/h 54 dB(A) -40 to +70 °C / -40 to +50 °C 20.7 kg
TCBT/6 H, 400 V 500 5604317900 930 min⁻¹ 198 W 0.5 A 4,990 m³/h 57 dB(A) -40 to +70 °C / -40 to +50 °C 24.8 kg
TCBT/6 H, 400 V 560 5605776600 920 min⁻¹ 363 W 0.8 A 7,630 m³/h 60 dB(A) -40 to +70 °C / -40 to +50 °C 33.5 kg
TCBT/6 H, 400 V 630 5603999500 950 min⁻¹ 906 W 2.7 A 13,610 m³/h 62 dB(A) -40 to +70 °C / -40 to +50 °C 38.5 kg
TCBT/6 H, 400 V 710 5605766400 910 min⁻¹ 1378 W 3.1 A 19,120 m³/h 63 dB(A) -40 to +70 °C / -40 to +40 °C 46.0 kg
TCBT/4 L, 400 V 560 5604307900 1415 min⁻¹ 1184 W 2.2 A 12,090 m³/h 68 dB(A) -40 to +70 °C / -40 to +50 °C 33.0 kg
TCBT/4 L, 400 V 630 5604308900 1410 min⁻¹ 1768 W 3.4 A 16,370 m³/h 70 dB(A) -40 to +70 °C / -40 to +40 °C 39.0 kg
TCBT/4 L, 400 V 710 5603928300 1435 min⁻¹ 2175 W 3.7 A 20,290 m³/h 73 dB(A) -40 to +40 °C / -40 to +40 °C 46.0 kg
TCBT/4 L, 400 V 800 5605768700 1460 min⁻¹ 3750 W 6.5 A 29,950 m³/h 76 dB(A) -40 to +40 °C / -40 to +40 °C 65.0 kg
TCBT/6 L, 400 V 630 5603999600 915 min⁻¹ 595 W 1.3 A 10,940 m³/h 60 dB(A) -40 to +70 °C / -40 to +50 °C 38.0 kg
TCBT/6 L, 400 V 710 5605766500 910 min⁻¹ 967 W 2.0 A 16,240 m³/h 62 dB(A) -40 to +70 °C / -40 to +40 °C 46.0 kg
TCBTx2/4 high pressure, 400 V 450 5605764900 1430 min⁻¹ 1309 W 3.0 A 7,250 m³/h 74 dB(A) 42 kg
TCBTx2/4 high pressure, 400 V 500 5605767700 1390 min⁻¹ 1700 W 3.4 A 9,800 m³/h 76 dB(A) 50 kg
TCBTx2/4 high pressure, 400 V 560 5605767800 1390 min⁻¹ 3173 W 5.8 A 15,170 m³/h 78 dB(A) 66 kg
TCBTx2/4 high pressure, 400 V 630 5605765100 1445 min⁻¹ 4014 W 7.4 A 17,810 m³/h 79 dB(A) 80 kg
TCBT/4 H-B, 400 V 250 5604294800 1470 min⁻¹ 42 W 0.2 A 900 m³/h 42 dB(A) -40 to +40 °C / -40 to +40 °C 8.0 kg
TCBT/4 G, 400 V 800 5605768500 1470 min⁻¹ 6146 W 11.1 A 38,500 m³/h 77 dB(A) -40 to +40 °C / -40 to +40 °C 81.0 kg
TCBT/4 K, 400 V 800 5605768600 1460 min⁻¹ 5177 W 8.8 A 34,950 m³/h 76 dB(A) -40 to +40 °C / -40 to +40 °C 68.0 kg
TCBB/2 H, 230 V 250 5705079600 2680 min⁻¹ 123 W 0.5 A 1,680 m³/h 62 dB(A) -40 to +40 °C / not specified 8.0 kg
TCBB/4 H, 230 V 250 5705079700 1430 min⁻¹ 44 W 0.2 A 900 m³/h 42 dB(A) -40 to +40 °C / -40 to +40 °C 8.0 kg
TCBB/4 H, 230 V 315 5705079800 1435 min⁻¹ 105 W 0.6 A 1,990 m³/h 52 dB(A) -40 to +40 °C / -40 to +40 °C 11.0 kg
TCBB/4 H, 230 V 355 5705079900 1420 min⁻¹ 120 W 0.6 A 2,460 m³/h 52 dB(A) -40 to +40 °C / -40 to +40 °C 13.2 kg
TCBB/4 H, 230 V 400 5740124200 1410 min⁻¹ 277 W 1.1 A 5,050 m³/h 60 dB(A) -40 to +70 °C / -40 to +40 °C 15.5 kg
TCBB/4 H, 230 V 450 5604636400 1410 min⁻¹ 591 W 2.5 A 6,940 m³/h 63 dB(A) -40 to +70 °C / not specified 21.0 kg
TCBB/4 H, 230 V 500 5604636300 1410 min⁻¹ 636 W 2.8 A 7,500 m³/h 66 dB(A) -40 to +70 °C / -40 to +50 °C 25.0 kg
TCBB/4 H, 230 V 560 5604634800 1400 min⁻¹ 1308 W 6.0 A 12,170 m³/h 69 dB(A) -40 to +70 °C / not specified 34.7 kg
TCBB/6 H, 230 V 355 5604656800 880 min⁻¹ 92 W 0.4 A 2,160 m³/h 46 dB(A) -40 to +40 °C / -40 to +40 °C 13.2 kg
TCBB/6 H, 230 V 400 5604331800 870 min⁻¹ 118 W 0.5 A 2,820 m³/h 48 dB(A) -40 to +40 °C / -40 to +40 °C 15.5 kg
TCBB/6 H, 230 V 500 5604633200 920 min⁻¹ 226 W 1.0 A 5,250 m³/h 57 dB(A) -40 to +70 °C / -40 to +50 °C 24.8 kg
TCBB/4 L, 230 V 560 5604634700 1405 min⁻¹ 1289 W 6.0 A 11,990 m³/h 68 dB(A) -40 to +70 °C / -40 to +50 °C 33.0 kg
TCBB/4 L, 230 V 630 5604638700 1365 min⁻¹ 1707 W 7.5 A 15,980 m³/h 70 dB(A) -40 to +70 °C / not specified 40.0 kg
TCBB/6 L, 230 V 560 5604636500 930 min⁻¹ 375 W 1.6 A 7,810 m³/h 60 dB(A) -40 to +70 °C / -40 to +50 °C 33.5 kg
TCBB/6 L, 230 V 630 5604639600 920 min⁻¹ 514 W 2.1 A 10,410 m³/h 60 dB(A) -40 to +70 °C / -40 to +50 °C 38.5 kg
TCBB/6 L, 230 V 710 5604633400 930 min⁻¹ 849 W 4.2 A 14,480 m³/h 62 dB(A) -40 to +70 °C / not specified 46.0 kg
TCBBx2/4 high pressure, 230 V 450 5605764700 1420 min⁻¹ 1316 W 5.7 A 7,430 m³/h 74 dB(A) 42 kg
TCBBx2/4 high pressure, 230 V 500 5605766800 1370 min⁻¹ 1957 W 9.0 A 9,950 m³/h 76 dB(A) 50 kg

Features

  • TCBT H, 400 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers with motor protection or frequency inverters.
  • TCBT H, 400 V: PM-55/3 NV maintenance switch as an accessory (3-pole with 2 auxiliary contacts, protection class IP67).
  • TCBT H, 400 V: Among the mounting accessories, S&P lists per size the DEF protective grille, FL counter flange, PIE mounting bracket, TAD inlet nozzle with protective grille, ELV flexible connection, TAA tubular silencer and TSK non-return damper (e.g. size 250: DEF-250 A, FL-250/435, PIE-250, TAD-250/435 N, ELV-250/435, TAA-250, TSK-250).
  • TCBT H, 400 V: Performance curves, sound power spectra and performance data according to ISO 5801 are included in the S&P data sheet.
  • TCBT L, 400 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers with motor protection or frequency inverters.
  • TCBT L, 400 V: PM-55/3 NV maintenance switch as an accessory (3-pole with 2 auxiliary contacts, protection class IP67).
  • TCBT L, 400 V: Among the mounting accessories, S&P lists per size the DEF protective grille, FL counter flange, PIE mounting bracket, TAD inlet nozzle with protective grille, ELV flexible connection, TAA tubular silencer and TSK non-return damper (e.g. size 560: DEF-560 A, FL-560, PIE-560, TAD-560 N, ELV-560, TAA-560, TSK-560).
  • TCBT L, 400 V: Performance curves, sound power spectra and performance data according to ISO 5801 are included in the S&P data sheet.
  • TCBTx2 high pressure, 400 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers or frequency inverters.
  • TCBTx2 high pressure, 400 V: PM-55/3 NV maintenance switch as an accessory.
  • TCBTx2 high pressure, 400 V: Among the mounting accessories, S&P lists per size the DEF protective grille, FL counter flange, PIE mounting bracket, TAD inlet nozzle with protective grille, ELV flexible connection, TAA tubular silencer and TSK non-return damper (e.g. size 450: DEF-450 A, FL-450, PIE-450, TAD-450 N, ELV-450, TAA-450, TSK-450).
  • TCBTx2 high pressure, 400 V: Performance curves and sound power spectra are included in the S&P catalogue.
  • TCBT H-B, 400 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers with motor protection or frequency inverters.
  • TCBT H-B, 400 V: PM-55/3 NV maintenance switch as an accessory (3-pole with 2 auxiliary contacts, protection class IP67).
  • TCBT H-B, 400 V: Among the mounting accessories, S&P lists the DEF-250 A protective grille, FL-250/435 counter flange, PIE-250 mounting bracket, TAD-250/435 N inlet nozzle with protective grille, ELV-250/435 flexible connection, TAA-250 tubular silencer and TSK-250 non-return damper.
  • TCBT H-B, 400 V: Performance curves, sound power spectra and performance data according to ISO 5801 are included in the S&P data sheet.
  • TCBT G, 400 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers with motor protection or frequency inverters.
  • TCBT G, 400 V: PM-55/3 NV maintenance switch as an accessory (3-pole with 2 auxiliary contacts, protection class IP67).
  • TCBT G, 400 V: Among the mounting accessories, S&P lists the DEF-800 A / DEF-800 D protective grille, FL-800 counter flange, PIE-800 mounting bracket, TAD-800 N inlet nozzle with protective grille, ELV-800 flexible connection, TAA-800 tubular silencer and TSK-800 non-return damper.
  • TCBT G, 400 V: Performance curves, sound power spectra and performance data according to ISO 5801 are included in the S&P data sheet.
  • TCBT K, 400 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers with motor protection or frequency inverters.
  • TCBT K, 400 V: PM-55/3 NV maintenance switch as an accessory (3-pole with 2 auxiliary contacts, protection class IP67).
  • TCBT K, 400 V: Among the mounting accessories, S&P lists the DEF-800 A / DEF-800 D protective grille, FL-800 counter flange, PIE-800 mounting bracket, TAD-800 N inlet nozzle with protective grille, ELV-800 flexible connection, TAA-800 tubular silencer and TSK-800 non-return damper.
  • TCBT K, 400 V: Performance curves, sound power spectra and performance data according to ISO 5801 are included in the S&P data sheet.
  • TCBB H, 230 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers with motor protection.
  • TCBB H, 230 V: PM-55/3 NV maintenance switch as an accessory (3-pole with 2 auxiliary contacts, protection class IP67).
  • TCBB H, 230 V: Among the mounting accessories, S&P lists per size the DEF protective grille, FL counter flange, PIE mounting bracket, TAD inlet nozzle with protective grille, ELV flexible connection, TAA tubular silencer and TSK non-return damper (e.g. size 250: DEF-250 A, FL-250/435, PIE-250, TAD-250/435 N, ELV-250/435, TAA-250, TSK-250).
  • TCBB H, 230 V: Performance curves, sound power spectra and performance data according to ISO 5801 are included in the S&P data sheet.
  • TCBB L, 230 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers with motor protection.
  • TCBB L, 230 V: PM-55/3 NV maintenance switch as an accessory (3-pole with 2 auxiliary contacts, protection class IP67).
  • TCBB L, 230 V: Among the mounting accessories, S&P lists per size the DEF protective grille, FL counter flange, PIE mounting bracket, TAD inlet nozzle with protective grille, ELV flexible connection, TAA tubular silencer and TSK non-return damper (e.g. size 560: DEF-560 A, FL-560, PIE-560, TAD-560 N, ELV-560, TAA-560, TSK-560).
  • TCBB L, 230 V: Performance curves, sound power spectra and performance data according to ISO 5801 are included in the S&P data sheet.
  • TCBBx2 high pressure, 230 V: According to the manufacturer, all-pole motor protection according to EN 60335-2-80 in combination with an MSD-2 motor protection switch (accessory); according to S&P this is not required when using 5-step transformers.
  • TCBBx2 high pressure, 230 V: PM-55/3 NV maintenance switch as an accessory.
  • TCBBx2 high pressure, 230 V: Among the mounting accessories, S&P lists per size the DEF protective grille, FL counter flange, PIE mounting bracket, TAD inlet nozzle with protective grille, ELV flexible connection, TAA tubular silencer and TSK non-return damper (e.g. size 450: DEF-450 A, FL-450, PIE-450, TAD-450 N, ELV-450, TAA-450, TSK-450).
  • TCBBx2 high pressure, 230 V: Performance curves and sound power spectra are included in the S&P catalogue.

¹ Sound pressure level in free field, measured at a distance of approx. three times the impeller diameter, at least 1.5 m.

Data sheets and manuals (PDF)

Note on reviews: Any visitor can submit a review using the form; a purchase is not required. Anyone who submits a review receives an email to confirm their email address. Reviews marked “Verified” come from customers who bought the product from us. We do not check other reviews for a purchase.

Recommendations

From our range

Selected products from ventilation, filter and pipe technology.

View all recommendations →