Description
Description
S&P IBW Warmwasser-Heizregister, Baugröße 200 bis 450 is a hot water heater for installation in rectangular ventilation ducts from the S&P IBW series. According to the manufacturer, the galvanised sheet steel housing with 20 mm standard flange fits the S&P duct fans; the air heater consists of aluminium fins pressed onto copper tubes.
According to the manufacturer, the heater should be installed on the pressure side of the fan. For each size, the types are available in a version with lower and one with higher heating output (suffix -2 or -3 or -4).
Technical data
Technical data
| Series | IBW |
|---|---|
| Installation | in rectangular ventilation ducts, according to the manufacturer preferably on the pressure side of the fan |
| Housing | galvanised sheet steel, 20 mm standard flange |
| Heat exchanger | aluminium fins pressed onto copper tubes |
| Operating pressure | max. 16 bar |
| Operating temperature | max. 150 °C |
| Reference values of the table | outdoor air 0 °C; flow/return 80/60 °C or 60/40 °C |
| Model | Article number | Duct connection W x H | Heating output 80/60 | Heating output 60/40 | Temperature rise 80/60 | Temperature rise 60/40 | Airflow | Water pressure drop 80/60 | Water flow 80/60 | Weight | Connection | Pump hot water control (accessory) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| IBW-200-2 | 5132838400 | 400 x 200 mm | 10.7 kW | 6.5 kW | 28 K | 16 K | 1,150 m³/h | 2 kPa | 470 l/h | 8.0 kg | 3/4" | PWW-N1 |
| IBW-200-4 | 5132838500 | 400 x 200 mm | 17.3 kW | 10.8 kW | 44 K | 27 K | 1,150 m³/h | 3 kPa | 760 l/h | 9.6 kg | 3/4" | PWW-N1 |
| IBW-225-2 | 5132838600 | 500 x 250 mm | 17.1 kW | 10.8 kW | 28 K | 17 K | 1,800 m³/h | 6 kPa | 750 l/h | 8.8 kg | 3/4" | PWW-N1 |
| IBW-225-4 | 5132838700 | 500 x 250 mm | 29.7 kW | 19.8 kW | 48 K | 33 K | 1,800 m³/h | 8 kPa | 1,300 l/h | 10.9 kg | 3/4" | PWW-N1 |
| IBW-250-2 | 5132838800 | 500 x 300 mm | 21.6 kW | 13.7 kW | 29 K | 18 K | 2,160 m³/h | 4 kPa | 950 l/h | 12.2 kg | 3/4" | PWW-N1 |
| IBW-250-4 | 5132838900 | 500 x 300 mm | 35.9 kW | 24.2 kW | 48 K | 33 K | 2,160 m³/h | 10 kPa | 1,580 l/h | 11.8 kg | 1" | PWW-N1 |
| IBW-285-2 | 5132839000 | 600 x 300 mm | 25.7 kW | 16.2 kW | 28 K | 18 K | 2,600 m³/h | 4 kPa | 1,130 l/h | 13.1 kg | 3/4" | PWW-N1 |
| IBW-285-4 | 5132839100 | 600 x 300 mm | 43.4 kW | 29.4 kW | 47 K | 31 K | 2,600 m³/h | 10 kPa | 1,900 l/h | 14.7 kg | 1" | PWW-N2 |
| IBW-315-2 | 5132839200 | 600 x 350 mm | 28.5 kW | 18.1 kW | 26 K | 18 K | 3,020 m³/h | 6 kPa | 1,250 l/h | 14.1 kg | 3/4" | PWW-N1 |
| IBW-315-4 | 5132839300 | 600 x 350 mm | 48.2 kW | 32.5 kW | 46 K | 31 K | 3,020 m³/h | 13 kPa | 2,120 l/h | 14.6 kg | 1" | PWW-N2 |
| IBW-355-2 | 5132839400 | 700 x 400 mm | 40.7 kW | 26.0 kW | 30 K | 18 K | 4,030 m³/h | 5 kPa | 1,790 l/h | 14.6 kg | 1" | PWW-N1 |
| IBW-355-3 | 5132839500 | 700 x 400 mm | 55.0 kW | 36.0 kW | 40 K | 26 K | 4,030 m³/h | 6 kPa | 2,410 l/h | 16.5 kg | 1" | PWW-N2 |
| IBW-400-2 | 5132839600 | 800 x 500 mm | 59.1 kW | 38.1 kW | 31 K | 18 K | 5,760 m³/h | 7 kPa | 2,600 l/h | 18.2 kg | 1" | PWW-N2 |
| IBW-400-4 | 5132839700 | 800 x 500 mm | 96.3 kW | 65.1 kW | 42 K | 27 K | 5,760 m³/h | 10 kPa | 4,230 l/h | 24.8 kg | 1" | not stated |
| IBW-450-2 | 5132839800 | 1000 x 500 mm | 75.1 kW | 49.0 kW | 30 K | 20 K | 7,200 m³/h | 7 kPa | 3,300 l/h | 20.3 kg | 1" | not stated |
| IBW-450-4 | 5132839900 | 1000 x 500 mm | 122.0 kW | 82.6 kW | 42 K | 28 K | 7,200 m³/h | 14 kPa | 5,370 l/h | 28.2 kg | 1" | not stated |
Features
Features
- According to the manufacturer, screw connections must be provided for the water connection; the heater must be able to be drained and vented during installation.
- According to the S&P safety note, a frost protection device must be provided which switches off the fan and, if necessary, closes a damper in the outdoor air if the air or return temperature is too low.
- To protect against contamination and loss of output, S&P recommends installing an air filter box.
- As accessories, S&P lists the PWW-N1 and PWW-N2 pump hot water controls (hydraulic unit with circulation pump, three-way mixer with 230 V actuator, shut-off valves and LHCC supply air temperature control); the matching unit for each type is shown in the table.
- Curves for temperature rise and pressure drop and the dimension drawing are given in the data sheet.
Note on variants
Note on variants
The "Model" selection shows the S&P type: the number after IBW is the size matching the duct connection in the table; the suffix -2, -3 or -4 distinguishes the output levels within a size. For IBW-400-4, IBW-450-2 and IBW-450-4, the data sheet does not list a matching pump hot water control.
Data sheets and manuals (PDF)